Description
Allen-Bradley 1492-CB1 H010 1A 1-Pole 277V Supplementary Protector Circuit Breaker
Single-pole supplementary protector circuit breaker rated for 1A at 277VAC. Provides overcurrent protection in industrial control and telecommunications applications. DIN rail mounted with H010 trip curve.
Specifications & What's Included
- Model: 1492-CB1 H010
- Current Rating: 1A
- Voltage: 277VAC / 65VDC
- Interrupting Capacity: 5000A rms (AC), 6000A (VDE DC)
- Mounting: DIN Rail
- Certifications: UL (E65138), VDE 2806, CSA, CE
- Manufactured in Switzerland
- Breaker unit only, no accessories included
Applications
Supplementary protectors are used in control circuits and low-current branch protection within industrial automation, PLC systems, and telecommunications equipment. This 1A rated unit handles auxiliary circuits, sensor inputs, and signal conditioning circuits where light-duty overcurrent protection is required. Compatible with standard DIN rail installations per IEC 947 specifications.
This Allen-Bradley 1492-CB1 H010 1A supplementary protector circuit breaker has been inspected and appears to be in good used condition. The unit shows normal handling wear consistent with prior industrial use. The DIN rail clip, toggle handle, and terminal connection points appear intact and undamaged. Please view our photo set and contact us if you have any questions. Please note: We have multiple units in stock — yours may not be the one shown in the photos, however, it will be similar in condition and function.
Warranty Information
Additional Information
Brand: |
Allen-Bradley |
Model: |
1492-CB1 |
MPN: |
1492-CB1 H010 |
Type: |
Supplementary Protector / Circuit Breaker |
SKU: |
47728 |
Series: |
Series B |
Current Rating: |
1A (1 Amp) |
Number of Poles: |
1 |
Voltage Rating (AC): |
277 Vac |
Voltage Rating (DC): |
65 Vdc |
Interrupting Capacity (AC): |
5000 A rms |
Interrupting Capacity (VDE DC): |
6000 A |
Trip Curve / Handle Code: |
H010 |
Mounting: |
DIN Rail |
Standards: |
IEC 934, 898, 950, IEC 947, UL (File E65138), VDE 2806 |
Certifications: |
UL, VDE, CSA, CE |
UL File Number: |
E65138 |
VDE Registration: |
No. 2806, 240/420 Vac |
Wire Temperature Rating: |
In ≤ 25A: 60/75°C; In > 25A: 75°C only |
Back-Up Fuse: |
In > 16A: 2.25 In |
Finger Safe: |
IEC 947 IP 2X |
Country/Region of Manufacture: |
Switzerland |
Condition: |
Used – Inspected |
Seller Notes: |
Single unit. Breaker only, no accessories included. |
Condition Notes: |
Allen-Bradley 1492-CB1 H010 1A supplementary protector. Inspected, good used condition. Normal handling wear. DIN rail clip, toggle, and terminals intact. Please view photos and contact us with questions. |